Part 3. Commissioning Procedure
108 Design Guide DCM014A51
2. Foreign Device
2.1 Foreign Device Setting
1. When the iTM BACnet® Server Gateway is on a different subnet from the BMS, a BACnet
Broadcast Management Device (BBMD) is required and the iTM BACnet Server Gateway should
be registered as a Foreign Device.
2. The iTM BACnet Server Gateway should also be configured with a BBMD IP address and Port
No.
2.2 Typically not changed unless requested by the BMS
1. The Foreign Device setting is only set if the BMS notifies that a BACnet Broadcast Management
Device (BBMD) is used on the network.
2. The iTM BACnet Server Gateway must be configured to communicate with the BBMD. This is
done by enabling the BBMD function, and adding the IP address of the BBMD and BBMD port
number to the CSV file (see section 4.2.1.8).
Figure 20. Enabling the BBMD