Part 3. Commissioning Procedure
116 Design Guide DCM014A51
i. BACnet® point setting “PNTSETTING.
1. Enable or disable each point as required to meet the controls specification.
Column
#
PNTSETTING_IN-H
(Title)
PNTSETTING_IN-D
(Default Value)
Comments
B
Pnt_Name
1:1-00
Indoor unit name - DO NOT CHANGE
C
Addr
1:1-00
Group Address - DO NOT CHANGE
D
Pny_ID
101
Assigned by iTM DO NOT CHANGE
E
Device_Instance
“Empty”
Assign unique device ID
F
Occupancy_Mode
1
1: Enable, 0: Disable
G
On_Off_Status
1
1: Enable, 0: Disable
H
Alarm_Status
1
1: Enable, 0: Disable
I
Operation_Mode
1
1: Enable, 0: Disable
J
Room_Temperature
1
1: Enable, 0: Disable
K
Occ_Cooling_Setpoint
1
1: Enable, 0: Disable
L
Occ_Heating_Setpoint
1
1: Enable, 0: Disable
M
Unocc_Cooling_Setpoint
1
1: Enable, 0: Disable
N
Unocc_Heating_Setpoint
1
1: Enable, 0: Disable
O
Max_Cooling_Setpoint
1
1: Enable, 0: Disable
P
Min_Cooling_Setpoint
1
1: Enable, 0: Disable
Q
Max_Heating_Setpoint
1
1: Enable, 0: Disable
R
Min_Heating_Setpoint
1
1: Enable, 0: Disable
S
Min_Setpoint_Differential
0
1: Enable, 0: Disable
T
Setpoint_Tracking_Mode
0
1: Enable, 0: Disable
U
Fan_Speed
0
1: Enable, 0: Disable
V
Airflow_Direction
0
1: Enable, 0: Disable
W
Timed_Override_Operation
0
1: Enable, 0: Disable
X
Current_Unit_Operation
0
1: Enable, 0: Disable
Y
RC_On_Off
1
1: Enable, 0: Disable
Z
RC_Operation_Mode
1
1: Enable, 0: Disable
AA
RC_Setpoint
1
1: Enable, 0: Disable
AB
Filter_Sign_Status
0
1: Enable, 0: Disable
AC
Filter_Sign_Reset
0
1: Enable, 0: Disable
AD
Indoor_Fan_Status
0
1: Enable, 0: Disable
AE
Communication_Status
0
1: Enable, 0: Disable
AF
Thermo_On_Status
0
1: Enable, 0: Disable
AG
Compressor_Status
0
1: Enable, 0: Disable
AH
Aux_Heater_Status
0
1: Enable, 0: Disable
AI
Forced_Thermo_Off
0
1: Enable, 0: Disable
AJ
Changeover_Option
0
1: Enable, 0: Disable

Table of Contents