Part 3. Commissioning Procedure
DCM014A51 Design Guide 119
i. Import error message details.
Type of Error
Error message
Detail of Error
Common setting
CSV File Version does not match.
There is no description of a file version
in CSV file.
There is an incorrect file version in the
CSV file.
No more than one common setting entry allowed.
There are multiple lines for Common
setting.
[Item]:File Error(line, column)
There is no numeric string.
[Item]:Out of Range(line, column)
There is out of range value.
Target
Device ID and
Object setting
(Management
Point individual
setting)
[Mgmt. Point ID]:Designated Management
Point does not exist(line, Column)
There is no-exist Management point ID.
[Mgmt. Point name] ([Mgmt. Point ID]) :[Item]:
File Error (line, column)
There is no numeric string.
[Mgmt. Point name] ([Mgmt. Point ID]) :[Item]:
Out of Range (line, column)
There is out of range value.
[Mgmt. Point name] ([Mgmt. Point ID]):
Duplicate Management Points (line, column)
There is the same Management point
ID.
[Mgmt. Point name] ([Mgmt. Point ID]) <->
[Mgmt. Point name] ([Mgmt. Point ID]) :
Duplicate Device_Instance_No (line, column)
There is same Device Instance Number
which is set to the other indoor unit.
[Mgmt. Point name] ([Mgmt. Point ID]) <->
Control_Device_Instance_No:
Duplicate Device_Instance_No (line, )
The same Device Instance Number is
used for System Control device.

Table of Contents