Part 3. Commissioning Procedure
DCM014A51 Design Guide 123
Handover to BMS
7.1 CSV File
1. Keep a copy of the CSV file with the proper configurations for record.
7.2 Network Settings
1. To allow the BMS to access the indoor unit information, change the iTM network settings
according to network administrator requirements. .
7.3 Ask the BMS integrator to discover the BACnet® points from the iTM.
7.4 Unable to auto discover BACnet points.
1. If the BMS cannot auto-discover the iTM BACnet points, the points must be manually entered
in the BMS system. The iTM BACnet Server Gateway Design Guide should be used as a source
for point information.
7.5 Final Review
1. Review points list with the BMS integrator to answer questions on how to use the BACnet
points.