Part 5. Installation Manual
DCM014A51 Design Guide 139
Appendix B. Supported Indoor Unit Models and Monitoring Control
Items
The following table includes a list of objects for each of the supported indoor unit models compatible
with the iTM BACne Server Gateway function.
Instance
No.
Object Name
VRV
Indoor
Unit
SkyAir
Indoor Unit
(except
FTXS)
Outdoor Air
Processing
Unit
Mini-Split &
SkyAir
FTXS Indoor
Units
(KRP928)
FFQ Indoor Unit
for Multi-Split &
Super Multi Plus
(DTA112BA51
adaptor may be
required)
1
Occupancy Mode
(Note4)
(Note4)
(Note4)
(Note4)
2
Unit On_Off Status
3
Alarm Status
4
Operation Mode
(Note3)
5
Room Temperature
(return air
temp)
6
Occ Cooling Setpoint
N/A
(Note1,2)
7
Occ Heating Setpoint
N/A
(Note1,2)
8
Unocc Cooling Setpoint
N/A
9
Unocc Heating Setpoint
N/A
10
Max Cooling Setpoint
N/A
11
Min Cooling Setpoint
N/A
12
Max Heating Setpoint
N/A
13
Min Heating Setpoint
N/A
14
Min Setpoint Differential
(Cooling & Heating)
N/A
15
Cooling & Heating Setpoint
Tracking Mode
N/A
16
Fan Speed
N/A
N/A
17
Airflow Direction
N/A
N/A
18
Timed Override Operation
19
Current Unit Operation
20
Remote Controller Prohibit
(On_Off)
21
Remote Controller Prohibit
(Operation Mode)
22
Remote Controller Prohibit
(Setpoint)
N/A
23
Filter Sign Status
N/A
24
Filter Sign Reset
N/A
25
Indoor Fan Status
N/A
26
Communication Status
27
Thermo-on Status
N/A
28
Compressor Status
N/A
29
Aux Heater Status
N/A
30
Forced Thermo-off
N/A
31
Indoor Unit Changeover Option