Part 2. Functional Specifications
30 Design Guide DCM014A51
4.5. Outdoor Unit Device
1. Each outdoor unit monitoring item (called object) is mapped to a BACnet object (called outdoor
unit object) and to an ObjectID instance number, as indicated in the table below.
2. Both of the objects types BI and MI set the text shown in the table below in the Description
Property in accordance with the value of Present_Value.
Common Outdoor Points
Instance
No.
Object_Name
Type
Inactive
Active
Remarks
Text-1
Text-2
Text-3
Text-4
Text-5
Text-6
Text-7
Text-8
1
Communication
Status
BI
Normal
Alarm
2
Operation Mode
MI
Cool
Heat
Fan
Heat &
Cool
3
Outdoor Unit Alarm
Status
BI
Normal
Alarm
Sets error code
in the
Description
Property
4
Defrost Mode
BI
Off
On
5
Oil Return
BI
Off
On
6
Electric Power
(calculated)
AI
*2
7
Electric Current
(calculated)
AI
*2
8
System Capacity Code
AI
*2
9
Outdoor Air
Temperature
AI
*1, *2