Part 2. Functional Specifications
DCM014A51 Design Guide 35
5. Properties
5.1 Device Object Type
Property Identifier
Property Datatype
Compatible
Class
Support
= Yes
= No
R: Readable
W: Writable
Remarks
Object_Identifier
BACnetObjectIdentifier
R
R
Configurable with
BACnet® Server/
Gateway Configuration
Object_Name
CharacterString
R
R
Indoor unit name*
Object_Type
BACnetObjectType
R
R
DEVICE
System_Status
BACnetDeviceStatus
R
R
Fixed to OPERATIONAL
Vendor_Name
CharacterString
R
R
DAIKIN Industries LTD
Vendor_Identifier
Unsigned16
R
R
Fixed to 53 (= DAIKIN)
Model_Name
CharacterString
R
R
Fixed to "Indoor Unit"
Firmware_Revision
CharacterString
R
R
Application_Software_
Version
CharacterString
R
R
Location
CharacterString
O
Description
CharacterString
O
R
Port No. + Group
Address connected to
DIII-NET
Ex: "1:1-00"
Protocol_Revision
Unsigned
R
R
Protocol_Services_
Supported
BACnetServiceSupported
R
R
RP, RPM, WP, WPM, I-
Am, I-Have, TimeSync,
Who-Is, Who-Has,
UTCTimeSync,
SubCOV
Protocol_Object_
Types_Supported
BACnetObjectTypesSupp
orted
R
R
AI, AV, BI, BV, MI, MO,
MV, Device
Object_List
BACnetARRAY[N] of
BACnetObjectIdentifier
R
R
Max_APDU_Length_
Accepted
Unsigned
R
R
1024
Segmentation_
Supported
BACnetSegmentation
R
R
SEGMENTED_BOTH
Max_Segments_
Accepted
Unsigned
O1
R
Fixed to 100
VT_Class_Supported
List of BACnetVTClass
O1
Active_VT_Sessions
List of BACnetVTSession
O2
Local_Time
Time
O3,4
R
Follows the iTM clock
Local_Date
Date
O3,4
R
Follows the iTM clock
UTC_Offset
Signed
O4
R
Follows the iTM clock
Daylight_Saving_Status
Boolean
O4
R
Follows the iTM clock
* The character code for indoor unit names is UTF-8