Part 2. Functional Specifications
DCM014A51 Design Guide 43
5.6 Binary Input Object Type
Property Identifier
Property Datatype
Compatible
Class
Support
= Yes,
= No
Remarks
Object_Identifier
BACnetObjectIdentifier
R
Object_Name
CharacterString
R
Object_Type
BACnetObjectType
R
BINARY_INPUT
Present_Value
BACnetBinaryPV
R1
Description
CharacterString
O
[Alarm Status]
Sets an error code
[Other]
Sets the string
corresponding to
the current value
Device_Type
CharacterString
O
Status_Flags
BACnetStatusFlags
R
IN_ALARM (Always
FALSE)
FAULT (TRUE:
Communication
error)
OVERRIDDEN
(Always FALSE)
OUT_OF_SERVICE
(Always FALSE)
Event_State
BACnetEventState
R
Fixed to NORMAL
Reliability
BACnetReliability
O
NO_FAULT_
DETECTED: Normal
communication
NO_SENSOR:
Sensor error
UNRELIABLE_
OTHER:
Communication
error
Out_Of_Service
Boolean
R
Always FALSE
Polarity
BACnetPolarity
R
Fixed to NORMAL
Inactive_Text
CharacterString
O2
Sets the string
corresponding to
Inactive
Active_Text
CharacterString
O2
Sets the string
corresponding to
Active
Change_Of_State_Time
BACnetDateTime
O3
Change_Of_State_Count
Unsigned
O3
Time_Of_State_Count_Reset
BACnetDateTime
O3
Elapsed_Active_Time
Unsigned32
O4
Time_Of_Active_Time_Reset
BACnetDateTime
O4
Time_Delay
Unsigned
O5
Notification_Class
Unsigned
O5
Alarm_Value
BACnetBinaryPV
O5
Event_Enable
BACnetEventTransitionBits
O5
Acked_Transitions
BACnetEventTransitionBits
O5
Notify_Type
BACnetNotifyType
O5
Event_Time_Stamps
BACnetARRAY[3] of
BACnetTimeStamp
O5
Profile_Name
CharacterString
O