Part 2. Functional Specifications
DCM014A51 Design Guide 45
5.8 Binary Value Object Type
Property Identifier
Property Datatype
Compatible
Class
Support
= Yes,
= No
R: Readable
W: Writable
Remarks
Object_Identifier
BACnetObjectIdentifier
R
R
Object_Name
CharacterString
R
R
Object_Type
BACnetObjectType
R
R
BINARY_VALUE
Present_Value
BACnetBinaryPV
R1
W
Description
CharacterString
O
R
Sets the string
corresponding to the
current value
Status_Flags
BACnetStatusFlags
R
R
IN_ALARM (Always
FALSE)
FAULT (TRUE:
Communication error)
OVERRIDDEN (Always
FALSE)
OUT_OF_SERVICE
(Always FALSE)
Event_State
BACnetEventState
R
R
Fixed to NORMAL
Reliability
BACnetReliability
O
R
NO_FAULT_DETECTED:
Normal
communication
UNRELIABLE_OTHER:
Communication error
Out_Of_Service
Boolean
R
R
Always FALSE
Inactive_Text
CharacterString
O2
R
Sets the string
corresponding to
Inactive
Active_Text
CharacterString
O2
R
Sets the string
corresponding to
Active
Change_Of_State_Time
BACnetDateTime
O3
Change_Of_State_Count
Unsigned
O3
Time_Of_State_Count_Reset
BACnetDateTime
O3
Elapsed_Active_Time
Unsigned32
O4
Time_Of_Active_Time_Reset
BACnetDateTime
O4
Minimum_Off_Time
Unsigned32
O
Minimum_On_Time
Unsigned32
O
Priority_Array
BACnetPriorityArray
R5
R
Relinquish_Default
BACnetBinaryPV
R5
R
Time_Delay
Unsigned
O6
Notification_Class
Unsigned
O6
Alarm_Value
BACnetBinaryPV
O6
Event_Enable
BACnetEventTransitionBits
O6
Acked_Transitions
BACnetEventTransitionBits
O6
Notify_Type
BACnetNotifyType
O6
Event_Time_Stamps
BACnetARRAY[3] of
BACnetTimeStamp
O6
Profile_Name
CharacterString
O

Table of Contents