EasyManua.ls Logo

Daikin intelligent Touch Manager BACnet DCM014A51 - Multi-State Output Object Type

Daikin intelligent Touch Manager BACnet DCM014A51
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part 2. Functional Specifications
DCM014A51 Design Guide 47
5.10 Multi-State Output Object Type
Property Identifier
Property Datatype
Compatible
Class
Support
= Yes,
= No
R: Readable
W: Writable
Remarks
Object_Identifier
BACnetObjectIdentifier
R
R
Object_Name
CharacterString
R
R
Object_Type
BACnetObjectType
R
R
MULTI-STATE_OUTPUT
Present_Value
Unsigned
W
W
Description
CharacterString
O
R
Sets the string
corresponding to the
current value
Device_Type
CharacterString
O
Status_Flags
BACnetStatusFlags
R
R
IN_ALARM (Always
FALSE)
FAULT (TRUE:
Communication error)
OVERRIDDEN (Always
FALSE)
OUT_OF_SERVICE
(Always FALSE)
Event_State
BACnetEventState
R
R
Fixed to NORMAL
Reliability
BACnetReliability
O
R
NO_FAULT_DETECTED:
Normal communication
UNRELIABLE_OTHER:
Communication error
Out_Of_Service
Boolean
R
R
Always FALSE
Number_Of_States
Unsigned
R
R
Sets the number of
states
State_Text
BACnetARRAY[N] of
CharacterString
O
R
Sets the string
corresponding to
Present_Value
Priority_Array
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
R
R
Time_Delay
Unsigned
O1
Notification_Class
Unsigned
O1
Feedback_Value
Unsigned
O1
Event_Enable
BACnetEventTransitionBits
O1
Acked_Transitions
BACnetEventTransitionBits
O1
Notify_Type
BACnetNotifyType
O1
Event_Time_Stamps
BACnetARRAY[3] of
BACnetTimeStamp
O1
Profile_Name
CharacterString
O