Part 2. Functional Specifications
86 Design Guide DCM014A51
*Objects other than those listed above, as well as, outdoor unit devices objects, are not supported by
COV.
The following error is returned to a SubscribeCOV request for an object that does not support COV:
Outdoor device: ErrorPDU (Class = OBJECT, Code = OPTIONAL_FUNCTIONALITY_NOT_SUPPORTED)
Indoor device: RejectPDU (UNRECOGNIZED_SERVICE)