EasyManua.ls Logo

Daikin intelligent Touch Manager BACnet DCM014A51 - Page 90

Daikin intelligent Touch Manager BACnet DCM014A51
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part 2. Functional Specifications
90 Design Guide DCM014A51
Standard Object Types Supported:
1. Analog Input
a. Return Air Temperature, Discharge Air Temperature, Liquid Pipe Temperature, Gas Pipe
Temperature, EV position, All Outdoor Unit's AI Object
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Reliability
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
b. Other
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Reliability, COV_Increment
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
2. Analog Value
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Reliability, Priority_Array, Relinquish_Default,
COV_Increment
Writable Properties: Present_Value
Proprietary Properties: N/A
Property Range Restrictions: N/A
3. Binary Input
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description, Reliability, Inactive_Text, Active_Text,
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
4. Binary Output
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description, Reliability, Inactive_Text, Active_Text,
Writable Properties: Present_Value
Proprietary Properties: N/A
Property Range Restrictions: N/A

Table of Contents