12. BACnet Gateway (BACnetGW) and iTM Protocol Comparison
This section describes the following differences between BACnetGW (Ver. 6.34.00) and iTM:
1. Functions removed from BACnetGW
2. Functions changed from BACnetGW
Note that "Additions from BACnetGW" are omitted from this section as they are described in the
main body of these specifications.
Furthermore, differences described in this section are limited to the following:
• Properties
• Services
• PICS
12.1. Functions removed from the BACnetGW
1. Properties
The following properties are not supported because Event is not supported:
a. Common (Analog Input, Binary Input, Binary Value)
Time_Delay
Notification_Class
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
b. Analog Input (Room Temperature)
High_Limit
Low_Limit
Deadband
Limit_Enable
c. Binary Input (Unit On_Off Status)
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
2. Services
The following services are removed because Unsolicited COV and Event are not supported:
Device Management-DeviceCommunicationControl-B
Data Sharing-COV-Unsolicited-B
Alarm and Event-Notification InternalB
Device Management - List ManipulationB