Time_Of_Active_Time_Reset
98 Design Guide DCM014A51
12.2. Functions changed from BACnetGW
Services changed because COV and Event are not supported.
Object
Type
Property Identifier
Before (BACnetGW
(Ver6.34.00))
After (iTM for North
America)
Property
Device
(for
indoor
unit)
Object_Name
DAIKIN MasterStation III
Indoor unit name
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRESS
Fixed to
OPERATIONAL
Model_Name
Fixed to "D-BACS BACnet
Gateway"
Fixed to "Indoor
Unit"
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP, WPM,
I-Am, I-Have, TimeSync, Who-
Is, Who-Has, UTCTimeSync
(DeviceCommunicationControl
*ver6.20 to)
(AddList, RemoveList *When
Event notification is
supported)
SubCOV, RP, RPM,
WP, WPM, I-Am,
TimeSync, Who-Is,
Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO, Device,NotificationClass
AI, AV, BI,BV, MI,
MO, MV, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings
Device
(for
system
control )
Object_Name
DAIKIN MasterStation III
Fixed to “Daikin ITM
Server Control”
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRESS
Normal: OPERATIONAL
Fixed to
OPERATIONAL
Model_Name
Fixed to “D-BACS BACnet
Gateway”
Fixed to “Daikin ITM
Server Control”
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP, WPM,
I-Am, I-Have, TimeSync, Who-
Is, Who-Has, UTCTimeSync
(DeviceCommunicationControl
*ver6.20 to)
(AddList, RemoveList *When
Event notification is
supported)
SubCOV, RP, RPM,
WP, WPM, I-Am,
TimeSync, Who-Is,
Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO, Device,NotificationClass
BO, MV, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings