* Follows the iTM software version.
DCM014A51 Design Guide 99
Continued from previous page
Object
Type
Property Identifier
Before (BACnetGW
(Ver6.34.00))
After (iTM for North
America)
Property
Device
(for
outdoor
unit)
Object_Name
DAIKIN MasterStation III
Outdoor unit name
System_Status
During D3 initialization:
DOWNLOAD_IN_PROGRE
SS
Fixed to
OPERATIONAL
Normal: OPERATIONAL
Model_Name
Fixed to “D-BACS BACnet
Gateway”
Fixed to “Outdoor
Unit”
Firmware_Revision
3000
Ver.000.001
Application_Software_Version
3000
*
Protocol_Services_Supported
SubCOV, RP, RPM, WP,
WPM, I-Am, I-Have,
TimeSync, Who-Is, Who-
Has, UTCTimeSync
(DeviceCommunicationCo
ntrol *ver6.20 to )
(AddList, RemoveList
*When Event notification
is supported
RP, RPM, I-Am,
TimeSync,
Who-Is, Who-Has,
UTCTimeSync
Protocol_Object_Types_Supported
AI, AO, AV, BI, BO, BV, MI,
MO,
Device,NotificationClass
AI, BI,MI, Device
Daylight_Saving_Status
Fixed to FALSE
Follows the iTM
clock settings