3 | Components
Service manual
80
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a Expansion valve motor
b Expansion valve motor harness
INFORMATION
The expansion valve and motor can have a different configuration / layout.
4 Cut all tie straps that fix the expansion valve motor harness.
5 Disconnect the expansion valve motor connector from the main PCB.
6 Pull up the expansion valve motor to remove it from the expansion valve
body.
INFORMATION
It may be needed to turn the expansion valve coil 1/8 turn counter clockwise to
unlock it. Make sure to note the correct orientation (position) of the expansion valve
coil before removal.
a bA
A Class 20~35 unit
a Expansion valve motor
b Expansion valve motor harness
a bA
A Class 42~71 unit
a Expansion valve motor
b Expansion valve motor harness