EasyManua.ls Logo

Daikin Perfera RXM35R - Page 198

Daikin Perfera RXM35R
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 | Components
Service manual
198
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
aA
A Wall mounted indoor unit
a Wifi control PCB assembly
aA
A Floor standing indoor unit
a Wifi control PCB assembly
Is the measured power supply voltage
correct?
Action
Yes Skip the next step..
No Continue with the next step.
4 Measure the output voltage between between the pins 4‑5 on the connector
S801 on the indoor unit main PCB.
Result: The measured voltage MUST be 10~16VDC.
Is the output voltage on the indoor unit
main PCB correct?
Action
Yes Replace the wifi control PCB wiring
harness, see "Repair
procedures"[4199].
No Perform a check of the indoor unit main
PCB, see "Checking procedures"[4102].
5 As there are no further check procedures for this component, perform a check
of the indoor unit main PCB to check if the wifi control PCB needs to be
replaced. See "Checking procedures"[4102].

Table of Contents

Related product manuals