3 | Components
Service manual
59
RXM20~71R + ARXM25~71R + FTXM20~71R + ATXM25~50R +
FVXM25~50A
Split New Perfera R32
ESIE20-11 – 2021.01
a
a
A
A Class 20~35 unit
a Compressor pipe
a
a
A
A Class 42~71 unit
a Compressor pipe
a
a
a Compressor pipe
7 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02MPa.