EasyManua.ls Logo

Daikin R30PUY2S - AF Drain Level above Limit

Daikin R30PUY2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
107
3.13
AF
Drain Level above Limit
Remote Controller Display
AF
Applicable Models
FMCQ, FMDQ
Method of Error Detection
Water leakage is detected based on float switch ON/OFF
operation while the compressor is in non-operation.
Error Decision Conditions
When the float switch changes from ON to OFF while the
compressor is in non-operation.
Supposed Causes
Humidifier unit (optional accessory) leaking
Defective drain pipe (upward slope, etc.)
Defective indoor unit PCB
Troubleshooting
YES
NO
Field
drain piping
has a defect such as
upward sloping.
Modify the drain
piping.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
A
humidifier
unit (optional
accessory) is installed
on the indoor
unit.
Check if the
humidifier unit is
leaking.
Replace the
indoor unit PCB.
NO