Si20-701_B Troubleshooting by Remote Controller
490
1. Power module checking
When using the analog type of multiple tester, make
measurement in resistance measurement mode in
the x1k
range.
No.
Measuring point
Criterion Remark
+-
1P3 U
2 to 15k2P3 V
3P3 W
4U P3
Not less
than
15k
(including)
It may take
time to
determine the
resistance due
to capacitor
charge or else.
5V P3
6W P3
7N3 U
8N3 V
9N3 W
10 U N3
2 to 15k11 V N3
12 W N3
When using the digital type of multiple tester, make
measurement in diode check mode ( ).
No.
Measuring point
Criterion Remark
+-
1P3 UNot less
than
1.2V
(including)
It may take time to
determine the voltage
due to capacitor
charge or else.
2P3 V
3P3 W
4U P3
0.3 to 0.7V
5V P3
6W P3
7N3 U
8N3 V
9N3 W
10 U N3 Not less
than
1.2V
(including)
It may take time to
determine the voltage
due to capacitor
charge or else.
11 V N3
12 W N3