6 | Installation
Installer reference guide
49
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1B – 2020.05
Component
Recommended circuit breaker B
Earth leakage circuit breaker MUST comply with applicable
legislation
Model A B
3MXM40 3- core cable 2.5mm
2
H05RN-F (60245 IEC 57)
H07RN-F (60245 IEC 66)
3- core cable 4.0mm
2
H07RN-F (60245 IEC 66)
16A
3AMXM52,
3AMXF52,
3MXF52,
3MXM52,
3MXF68,
3MXM68,
4MXM68
20A
4MXM80 3- core cable 4.0 mm
2
H07RN-F (60245 IEC 66)
25A
5MXM90 32A
Electrical equipment must comply with EN/IEC 61000-3-12, the European/
International Technical Standard setting the limits for harmonic currents produced
by equipment connected to public low-voltage systems with input current >16 A
and ≤75 A per phase.
6.7.5 To connect the electrical wiring to the outdoor unit
1 Remove the switch box cover (1 screw).
2 Strip insulation (20mm) from the wires.
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Connect the wires between the indoor and outdoor units so that the terminal
numbers match. Make sure to match the symbols for piping and wiring.
4 Make sure to connect correct wiring to correct room.