Si20-701_B Troubleshooting by Remote Controller
98
3.9
A7
Swing Flap Motor
Abnormality / Lock
Remote Controller Display
A7
Applicable Models
FH(Y)C, FH(Y)K, FH(Y), FA(Y), FV(Y), FUY, FHC, FH,
FDBG, FDBT, FDMG, FCQ(H), FMCQ, FFQ, FHQ,
FAQ(except FAQ71BU), FBQ, FUQ, FVQ
Method of Error Detection
The error is detected by the limit switch when the motor
turns.
Error Decision Conditions
When ON/OFF of the micro-switch for position detection
cannot be reversed even though the swing flap motor is
energized for a specified amount of time (about 30
seconds).
Supposed Causes
Defective swing flap motor
Defective micro-switch
Defective connector connection
Defective indoor unit PCB