EasyManua.ls Logo

Daikin R36PUY2S - L5 Output Overcurrent Detection

Daikin R36PUY2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si20-701_B Troubleshooting by Remote Controller
284
3.63
L5
Output Overcurrent
Detection
Remote Controller Display
L5
Applicable Models
RZQG
Method of Error Detection
The error is detected by converting the current flowing to
power transistor into voltage with CT1 (DC current
sensor).
Error Decision Conditions
When overcurrent has run to power transistor.
(Actuated even by instantaneous overcurrent)
Supposed Causes
Defective compressor (mechanical lock, poor
insulation)
Defective inverter PCB
Instantaneous fluctuation of power supply voltage
Defective compressor (if bearing is scratched)
Stop valve is not opened

Table of Contents

Related product manuals