Troubleshooting by Remote Controller Si20-701_B
339
3.80
PJ
Field Setting Error after
Replacing Main PCB or
Defective Combination of PCB
Remote Controller Display
PJ
Applicable Models
CMSQ
Method of Error Detection
The defective (or no) field setting after replacing PCB or
defective PCB combination is detected through
communications with the inverter.
Error Decision Conditions
Whether or not the field setting or the type of the PCB is
correct through the communication date is judged.
Supposed Causes
Defective (or no) field setting after replacing main PCB
Mis-matching of type of PCB