Troubleshooting by Remote Controller Si20-701_B
293
Note:
1. Approximate value
When operating compressor with compressor output line
disconnected, the compressor stops due to error after
elapsed time of 5 seconds. Therefore, check the voltage
increase for 5 seconds.
Model Instantaneous overcurrent detection value
RZQ71K, RZR71K
RZQ71B9V3B
RZQS71·100B7V3B
RZQ71C7V1B
RZQS71·100C7V1B
32.0A
RZQ100-160H
RZQ100-140B8W1B
32.3A
RZR100-140HUY1
RZR-KUV2S
RZR-HUY2S
RZQ100-140C7V1B
RZQS125·140C7V1B
51.7A