Si20-701_B Troubleshooting by Remote Controller
104
1: Coil check method for the electronic expansion valve
coil
Disconnect the electronic expansion valve from the PCB
and check the continuity between the connector pins.
(Normal)
{: Continuity
× : No continuity
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
× {
Approx.
300
× {
Approx.
150
×
2. Yellow
× {
Approx.
300
× {
Approx.
150
3. Orange
× {
Approx.
150
×
4. Blue
× {
Approx.
150
5. Red ×
6. Brown