Daikin R48NUY2S - J1 Pressure Sensor Abnormality

Daikin R48NUY2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
241
3.47
J1
Pressure Sensor
Abnormality
Remote Controller Display
J1
Applicable Models
RZQ-K, RZQ(S)-C, RZR-KU/HU
Method of Error Detection
The error is detected by the pressure measured with
pressure sensor
Error Decision Conditions
When the detect pressure becomes following;
Detected pressure – 0.05MPa continues 185 sec.
Detected pressure 4.4MPa continues 185 sec.
Supposed Causes
Defective pressure sensor
Defective outdoor unit PCB
Incorrect connection of connector