Si20-701_B Troubleshooting by Remote Controller
330
Troubleshooting
Note:
1. Target : ±10V between phases, R-S, S-T, T-R
Check LED on
the outdoor unit PCB
(Open phase?)
NO
External factor.
Open phase
of power supply
voltage?
YES
NO
YES
Field factors.
Is the
voltage
imbalance
between phases
large? (1)
NO
YES
Field factors.
Replace the
outdoor inverter
PCB.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.