Daikin R48NUY2S - U4 Transmission Error between Indoor Unit and Outdoor Unit

Daikin R48NUY2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
381
3.93
U4
Transmission Error
Between Indoor Unit and
Outdoor Unit
Remote Controller Display
U4
Applicable Models
RZ(Y)
Method of Error Detection
Micro-computer checks if transmission between indoor
and outdoor units is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
Wiring indoor-outdoor transmission wire is incorrect.
Defective indoor unit PCB
Defective outdoor unit PCB
External factor (Noise, etc.)
Power supply -open phase