EasyManua.ls Logo

Daikin R48NUY2S - Page 438

Daikin R48NUY2S
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting by Remote Controller Si20-701_B
431
Troubleshooting
Note:
1. Only for pair/twin/triple/double twin
YES
NO
YES
NO
Is the
remote controller
connected to more
than 1 indoor
unit?
Connect the
remote controller
correctly.
NO
YES
Is the
setting of
Pair/Twin/Triple set
correctly?
Set correctly.
YES
NO
Are the
micro-computer
normal monitors
(HAP) of all indoor
unit PCB
blinking?
Connect
correctly.
Is the
indoor-indoor (1)
and indoor-outdoor
jumper correctly
connected?
NO
YES
YES
Connect
correctly.
Is the
power supply
PCB correctly
connected?
NO
Replace the
transformer.
Wiring could be
incorrect;
recheck.
Is
there 220-
240 VAC between
No.1 and No.3 of X2M
(indoor Unit)?
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
A

Table of Contents

Related product manuals