Main Functions SiBE041010
18 Function and Control
1.4 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
Detail The microcomputer automatically sets the temperature and airflow rate. The difference between
the room temperature at start-up and the target temperature is divided into two zones. Then, the
unit operates in the dry mode with an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
Room temperature at
start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24ºC or more
Room temperature at
start-up
X
2.5ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
23.5ºC
X
2.0ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
~
18ºC
18ºC X
2.0ºC
X
0.5ºC = 17.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
17.5ºC
~
Z
X
Y
Zone B
Zone B
Zone A = Thermostat OFF
Zone C = Thermostat ON
+0.5ºC
(R11581)