EDUS281120_a Installation of indoor unit
RZR-P, RZQ-P(9) 135
3P161684-6K
English 23
9-4 Computerized control (forced off and on/off operation)
(1) Wire specifications and how to perform wiring
Connect the input from outside to terminals T1 and T2 of the terminal block for remote controller.
(2) Actuation
The following table explains FORCED OFF and ON/OFF OPERATIONS in response to Input A.
(3) How to select FORCED OFF and ON/OFF OPERATION
Turn the power on and then use the remote controller to select operation.
9-5 Centralized control
For centralized control, it is necessary to designate the group No. For details, refer to the manual of each
optional controllers for centralized control.
10. INSTALLATION OF THE DECORATION PANEL
<If performing a test run without attaching the decoration panel, read “11. FIELD SETTING” and “12. TEST
RUN” first.>
Refer to the installation manual attached to the decoration panel.
After installing the decoration panel, ensure that there is no space between the unit body and decoration panel.
Note:
Since the electric insulation sheet stacked to the control box cover gets sandwiched between the unit body and
decoration panel, when closing the cover, slip the insulation sheet between them first and then attach the cover
to the control box.
Wire specificationCONDUCTORSTRANDEDNONSHIELDEDCOPPER06#ORVINYLJAKCET
Gauge AWG18 -
Length Max. 328ft.
External terminal Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.
FORCED OFF ON/OFF OPERATION
Input “ON” stops operation (impossible by remote controllers.) Input OFF ON turns ON unit.
Input OFF enables control by remote controller. Input ON OFF turns OFF unit.
F2 T1 T2
FORCED
OFF
Input A