EDUS281120_a Capacity tables
RZR-P, RZQ-P(9) 71
FBQ42PVJU + RZR42PVJU
Indoor Air Temp.
Outdoor Air Temp.
°FDB
68 77 86 90 95 104
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
°FDB °FWB kBTUH MBh kW kBTUH MBh kW kBTUH MBh kW kBTUH MBh kW kBTUH MBh kW kBTUH MBh kW
68.0 57.0 27.27 23.1 1.59 27.27 23.1 1.73 27.27 23.1 2.00 27.27 23.1 2.13 27.27 23.1 2.30 27.27 23.1 2.64
72.0 61.0 33.19 27.1 1.93 33.19 27.1 2.19 33.19 27.1 2.56 33.19 27.1 2.73 33.19 27.1 2.96 33.19 27.1 3.43
77.0 64.0 37.54 29.6 2.21 37.54 29.6 2.59 37.54 29.6 3.02 37.54 29.6 3.23 37.54 29.6 3.51 37.54 29.6 4.08
80.0 67.0 42.00 31.6 2.56 42.00 31.6 3.02 42.00 31.6 3.52 42.00 31.6 3.78 42.00 31.6 4.12 40.34 30.8 4.46
86.0 72.0 48.53 32.6 3.12 46.77 31.8 3.47 45.11 31.1 3.81 44.28 30.7 3.96 43.35 30.3 4.17 41.69 29.4 4.52
90.0 75.0 49.36 31.5 3.14 47.60 30.6 3.49 45.94 29.8 3.84 45.11 29.4 3.99 44.18 29.0 4.19 42.52 28.1 4.55
Cooling Capacity
230V–60Hz
Cooling
Indoor : 80˚FDB, 67˚FWB
Outdoor : 95˚FDB
Equivalent Piping Length
25ft (Level Difference : 0)
Hz, Volts
60Hz, 230V
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. shows nominal MAX capacities

Other manuals for Daikin SkyAir FHQ24PVJU