Outdoor Unit: 3MXS24JVJU, 4MXS32GVJU SiUS12-928_B
235 Removal Procedure
4
Disconnect the connector
for the four-way valve coil
[S80].
Pull out the clamp.
5
Disconnect the 4
connectors for the
electronic expansion
valve coils (for room A, B,
C, D) and pull out the
clamp.
A : [S20] (white)
B : [S21] (red)
C : [S22] (blue)
D : [S23] (yellow)
The 3MXS model does not
have [S23].
When reassembling, insert
each clamp into the hole.
6
Disconnect the connector
for the liquid pipe
thermistors [S93] and pull
out the clamp.
Step
Procedure Points
[S80]
Clamp
(R10398)
A
B
C
D
Clamp
(R10399)
For the electronic
expansion valve coil
[S93]
(R17354)
Clamp
[S93]
(R10400)