InstallationGuideECLComfort210/310,applicationA214/A314

87 H14 94 .10
Da nfos s
X
# 5 #
# 3 #
# 4 #
# 2 #
# 1 #






MENU>Settings>Application
StopatTout
1x038
CircuitSettingrange
Factorysetting
All
**
Whentheoutdoortemperaturegetshigherthansetlimit,therelated
functionisenabled.

Value:


OFF:

MENU>Settings>Application
MENU>Settings>Fan/acc.control
PfrostT(circulationpump,frostprotectiontemp.)
1x077
CircuitSettingrange
Factorysetting
All
**
Frostprotection,basedontheoutdoortemperature.
Whentheoutdoortemperaturegetsbelowthesettemperaturevaluein‘P
frostT ,thecontrollerautomaticallyswitchesONthecirculationpump(for
exampleP1orX3)toprotectthesystem.

OFF:

Value:










