2
FRCC.EI.026.A2.02 © Danfoss Commercial Compressors 11/12
Instructions
5 – Leak detection
  Never  pressurize  the  circuit with oxygen  or 
dry air. This could cause re or explosion.
  •  Do not use dye for leak detection.
  •  Perform a leak detection test on the complete 
system.
  •  The maximum test pressure is 32 bar.
  •  When a leak is discovered, repair the leak and 
repeat the leak detection.
6 – Vacuum dehydration
  •  Never use the compressor to evacuate the system.
  •  Connect a vacuum pump to both the LP & HP 
sides.
  •  Pull down the system under a vacuum of 500 
μm Hg (0.67 mbar) absolute.
  •  Do not use a megohmmeter nor apply power 
to the compressor while it is under vacuum as 
this may cause internal damage.
7 – Electrical connections
  •  Switch o and isolate the main power supply.
  •  Ensure that power supply can not be switched 
on during installation.
  •  All electrical components must be selected as 
per local standards and unit requirements.
  •  Refer to wiring diagram for electrical connec-
tions details.
  •  Ensure that the power supply corresponds to 
the  unit  characteristics  and  that  the  power 
supply  is  stable  (nominal  voltage  ±10%  and 
nominal frequency ±2,5 Hz).
  •  Dimension  the  power  supply  cables  accor-
ding to unit data for voltage and current.
  •  Protect the power supply and ensure correct 
earthing.
  •  Make  the  power  supply  according  to  local 
standards and legal requirements.
  •  The unit is equipped with high and low pres-
sure  switches,  which  directly  cut  the  power 
supply to the compressor in case of activation.
Parameters for high and low pressure cut outs 
should  be  set  by  installer  considering  com-
pressor model, refrigerant and application.
For units with a 3-phase scroll compressor, cor-
rect  phase  sequence  for  compressor  rotation 
direction shall be observed.
  •  Determine  the  phase  sequence  by  using  a 
phase  meter  in  order  to  establish  the  phase 
orders of line phases L1, L2 and L3.
  •  Connect  line  phases  L1,  L2  and  L3  to  main 
switch terminals T1, T2 and T3 respectively.
8 – Filling the system
  •  Wear protective stu like goggles and protec-
tive gloves.
  •  Never  start  the  compressor  under  vacuum. 
Keep the compressor switched o.
  •  Before charging the refrigerant, verify that the 
oil level is between ¼ and ¾ on the compressor 
oil sight glass. If additional oil is required please 
refer to the compressors label for type of oil.
  •  Use only the refrigerant for which  the unit is 
designed for.
  •  Fill  the  refrigerant  in  liquid  phase  into  the 
condenser  or  liquid  receiver.  Ensure  a  slow 
charging of the system to 4 – 5 bar for R404A / 
R507A or R22 and approx. 2 bar for R134a.
  •  Do not put liquid refrigerant through suction line.
  •  It is not allowed to mix additives with the oil 
and/or refrigerant
  •  The remaining charge is done until the instal-
lation  has  reached  a  level  of  stable  nominal 
condition during operation.
  •  Never leave the lling cylinder  connected to 
the circuit.
9 – Verification before commissioning
  Use  safety  devices  such  as  safety  pressure 
switch  and  mechanical  relief  valve  in  com-
pliance  with  both  generally  and  locally  appli-
cable  regulations  and  safety  standards.  Ensure 
that they are operational and properly set.
  Check  that  the  settings  of  high-pressure 
switches and relief valves don’t exceed the maxi-
mum service pressure of any system component.
  •  Verify that  all electrical  connections  are properly 
fastened and in compliance with local regulations.
  •  When a  crankcase heater is required, it must 
be  energized  at  least  12  hours  before  initial 
start-up  and  start-up  after  prolonged  shut-
down or belt type crankcase heaters.
10 – Start-up
  •  Never  start  the  unit  when  no  refrigerant  is 
charged.
  •  All service valves must be in the open position.
See picture 3.
  •  Check  compliance  between  unit  and  power 
supply.
  •  Check that the crankcase heater is working.
  •  Check that the fan can rotate freely.
  •  Check that the protection sheet has been re-
moved from the backside of condenser.
  •  Balance the HP/LP pressure.
  •  Energize  the  unit.  It  must  start  promptly.  If 
the  compressor  does  not  start,  check wiring 
conformity,  voltage  on  terminals  and  se-
quence phase.
  •  Eventual reverse rotation of    a  3-phase  com-
pressor  can  be  detected  by  following  phe-
nomena;  unit  doesn’t  start,  the  compressor 
doesn’t  build  up  pressure, it  has  abnormally 
high sound  level  and  abnormally low power 
consumption.  In  such  case,  shut  down  the 
unit immediately and connect the  phases  to 
their proper terminals.
  •  If the rotation direction is correct the low pres-
sure  indication  on  the  low  pressure  gauge 
shall show a declining pressure and the high 
pressure  indication  on  the  high  pressure 
gauge shall show an increasing pressure.
11 – Check with running unit
  •  Check the fan rotation direction. Air must ow 
from the condenser towards the fan.
  •  Check current draw and voltage.
  •  Check  suction  superheat  to  reduce  risk  of 
slugging.
  •  When a sight glass is provided observe the oil 
level at start and during operation to conrm 
that the oil level remains visible.
  •  Respect the operating limits.
  •  Check all tubes for abnormal vibration. Move-
ments in excess of 1.5 mm require corrective 
measures such as tube brackets.
  •  When  needed,  additional  refrigerant  in  liquid 
phase may be added in the low-pressure side as 
far away as possible from the compressor. The 
compressor must be operating during this pro-
cess.
  •  Do not overcharge the system.
  •  Never release refrigerant to atmosphere.
  •  Before leaving  the  installation site, carry out 
a  general  installation  inspection  regarding 
cleanliness, noise and leak detection.
  •  Record type and amount of refrigerant charge 
as well as operating conditions as a reference 
for future inspections.
12 – Maintenance
 Always switch o the unit at main switch be-
fore remove fan panel.
  Internal  pressure  and  surface  temperature 
are dangerous and may cause permanent injury.
Maintenance  operators  and  installers  require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.
  Ensure  that  periodic  service  inspections  to 
ensure system reliability and as required by local 
regulations are performed.
To prevent system related problems, following
Periodic  maintenance is recommended:
  •  Verify that safety devices are operational and 
properly set.
  •  Ensure that the system is leak tight.
  •  Check the compressor current draw.
  •  Conrm that the system is operating in a way 
consistent  with  previous  maintenance  re-
cords and ambient conditions.
  •  Check  that  all  electrical  connections  are  still 
adequately fastened.
  •  Keep the unit clean and verify the absence of 
rust  and  oxidation  on  the  unit  components, 
tubes and electrical connections.
The  condenser  must  be  checked  at  least  once 
a  year  for  clogging  and  be  cleaned  if  deemed 
necessary.  Access  to  the  internal  side  of  the 
condenser  takes  place  through  the  fan  panel. 
Microchannel  coils  tend to  accumulate  dirt  on 
the  surface  rather  than  inside,  which  makes 
them easier to clean than n-&-tube coils.
  •  Switch o  the unit at main switch before re-
move any panel from the condensing unit.
  •  Remove  surface  dirt,  leaves,  bres,  etc.  with 
a vacuum cleaner, equipped  with  a  brush or 
other  soft  attachment.  Alternatively,  blow 
compressed air through the coil from the in-
side out, and brush with a soft bristle. Do not 
use a wire brush. Do not impact or scrape the 
coil with the vacuum tube or air nozzle.
If the refrigerant system  has been opened, the 
system has to be ushed with dry air or nitrogen 
to remove moisture and a new lter drier has to
be  installed.  If evacuation of refrigerant has  to 
be done, it shall be done in such a way that no 
refrigerant can escape to the environment.
13 - Warranty
Always transmit the model number and serial num-
ber with any claim led regarding this product.
The product warranty may be void in following 
cases:
  •  Absence of nameplate.
  •  External  modications;  in  particular,  drilling, 
welding, broken feet and shock marks.
  •  Compressor opened or returned unsealed.
  •  Rust,  water  or  leak  detection  dye  inside  the 
compressor.
  •  Use of a refrigerant or lubricant not approved 
by Danfoss.
  •  Any  deviation  from  recommended  instruc-
tions pertaining to installation, application or 
maintenance.
  •  Use in mobile applications.
  •  Use in explosive atmospheric environment.
  •  No model number or serial number transmit-
ted with the warranty claim.
14 – Disposal
Danfoss recommends that condensing 
units  and  oil  should  be  recycled  by  a 
suitable company at its site.