EasyManua.ls Logo

Danfoss VLT 5011 - Page 45

Danfoss VLT 5011
45 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
Wiring
Serial Communications
Need repeater (amplifier) after 31 drives attached together
Dip switch settings 2 & 3 to OFF except for 2 bus ends
Serial Communications
This diagram shows how the serial communications is wired. Notice that it is an RS-
485 connection, which means that all the positive terminals (68) are wired together and all
the negatives (69) are wired together. These connections must be in a “Daisy Chain”
fashion which only has 2 ends. Star configurations should NOT be used. The address for
each drive is set in parameter 500, from address 1 to 126. The default address is #1. If
more than 31 drives are attached a repeater should be used to amplify the signal.
On the control card just above the serial communications plug, there is a DIP switch,
which is used to enable/disable the EOL (end of line) resistor. If one or 2 drives are attached
together, leave the DIP alone. Once a 3
rd
drive is added, the middle drive must have
switches 2 and 3 turned OFF, down, to remove the EOL resistor. If other drives are added,
all drive that are not on the 2 ends must have DIP switch settings 2 and 3 turned OFF.

Other manuals for Danfoss VLT 5011

Related product manuals