Compact, AC line supply 3 x 380-500 V
According to international requirements VLT type 5032 5042 5052
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (380-440 V)
61 73 90
I
VLT, MAX
(60 s) [A] (380-440 V)
67.1 80.3 99
I
VLT,N
[A] (441-500 V)
54 65 78
I
VLT, MAX
(60 s) [A] (441-500 V)
59.4 71.5 85.8
Output
S
VLT,N
[kVA] (380-440 V)
46.5 55.6 68.6
S
VLT,N
[kVA] (441-500 V)
46.8 56.3 67.5
Typical shaft output
P
VLT,N
[kW]
30 37 45
Typical shaft output
P
VLT,N
[HP]
40 50 60
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-440 V)
44 61 73
I
VLT, MAX
(60 s) [A] (380-440 V)
70.4 97.6 116.8
I
VLT,N
[A] (441-500 V)
41.4 54 65
I
VLT, MAX
(60 s) [A] (441-500 V)
66.2 86 104
Output
S
VLT,N
[kVA] (380-440 V)
33.5 46.5 55.6
S
VLT,N
[kVA] (441-500 V)
35.9 46.8 56.3
Typical shaft output
P
VLT,N
[kW]
22 30 37
Typical shaft output
P
VLT,N
[HP]
30 40 50
Max. cable cross-section to motor, IP 54 35/2 35/2 50/0
brake and load sharing [mm
2
]/[AWG]
2) 5)
IP 20 35/2 35/2 50/0
Min. cable cross-section to motor,
brake and load sharing [mm
2
]/[AWG]
2) 4)
10/8 10/8 16/6
Rated input current
I
L,N
[A] (380 V)
60 72 89
I
L,N
[A] (460 V)
53 64 77
Max. cable cross-section IP 54 35/2 35/2 50/0
power[mm
2
]/[AWG]
2) 5)
IP 20 35/2 35/2 50/0
Max. pre-fuses
[-]/UL
1)
[A]
80/80 100/100 125/125
Efficiency
3)
0.96 0.96 0.96
Weight IP 20 EB [kg] 28 41 42
Weight IP 54 [kg] 54 56 56
Power loss at max. load.
- high overload torque (160 %)
[W] 768 1065 1275
- normal overload torque (110 %) [W] 1065 1275 1571
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
5. Aluminum cables with cross-section above 0.054 in
2
[35 mm
2
] must be connected by use of an AI-Cu connector.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 19
Technical data

Table of Contents

Other manuals for Danfoss VLT 5016

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5016 and is the answer not in the manual?

Danfoss VLT 5016 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5016
CategoryDC Drives
LanguageEnglish

Related product manuals