4.3 Overview of Enclosures, 380–500 V
Enclosure size D1h D2h D3h D4h D5h D6h D7h D8h
Power rating
1)
Output at 400 V (kW) 90–132 160–250 90–132 160–250 90–132 90–132 160–250 160–250
Output at 460 V (hp) 125–200 250–350 125–200 250–350 125–200 125–200 250–350 250–350
Protection rating
IP IP21/54 IP21/54 IP20 IP20 IP21/54 IP21/54 IP21/54 IP21/54
NEMA Type 1/12 Type 1/12 Type Chassis Type Chassis Type 1/12 Type 1/12 Type 1/12 Type 1/12
Hardware options
2)
Stainless steel back
channel
O O O O O O O O
Mains shielding O O – – O O O O
Space heater O O – – O O O O
RFI lter (Class A1) O O O O O O O O
Safe torque o S S S S S S S S
No LCP O O O O O O O O
Numerical LCP O O O O O O O O
Graphical LCP O O O O O O O O
Fuses O O O O O O O O
Heat sink access
3)
O O O O O O O O
Brake chopper – – O O O O O O
Regeneration terminals – – O O O O O O
Loadshare terminals – – O O – – – –
Fuses + loadshare – – O O – – – –
Disconnect – – – – – O – O
Circuit breakers – – – – – O – O
Contactors – – – – – O – O
24 V DC supply O O O O O O O O
Dimensions
Height, mm (in) 901 (35.5) 1107 (43.6) 909 (35.8)
1004 (39.5)
4)
1027 (40.4)
1027 (40.4)
4)
1324 (52.1) 1663 (65.5) 1978 (77.9) 2284 (89.9)
Width, mm (in) 325 (12.8) 325 (12.8) 250 (9.8) 375 (14.8) 325 (12.8) 325 (12.8) 420 (16.5) 420 (16.5)
Depth, mm (in) 379 (14.9) 379 (14.9) 375 (14.8) 375 (14.8) 381 (15.0) 381 (15.0) 386 (15.2) 406 (16.0)
Weight, kg (lb) 62 (137) 125 (276) 62 (137)
108 (238)
4)
125 (276)
179 (395)
4)
99 (218) 128 (282) 185 (408) 232 (512)
Table 4.3 D1h–D8h Drives, 380–500 V
1) All power ratings are taken at high overload. Output is measured at 400 V (kW) and 460 V (hp).
2) S = standard, O = optional, and a dash indicates that the option is unavailable.
3) Heat sink access is not available with stainless steel back-channel option.
4) With optional load share and regen terminals.
Product Overview VLT® AutomationDrive FC 302
12 Danfoss A/S © 01/2018 All rights reserved. MG38C202