Enclosure size E1h E2h E3h E4h
Power rating
1)
Output at 400 V (kW) 315–400 450–500 315–400 450–500
Output at 460 V (hp) 450–550 600–650 450–550 600–650
Protection rating
IP IP21/54 IP21/54
IP20
2)
IP20
2)
UL type Type 1/12 Type 1/12 Chassis Chassis
Hardware options
3)
Stainless steel back channel O O O O
Mains shielding O O – –
Space heater O O – –
RFI lter (Class A1) O O O O
Safe torque o S S S S
No LCP O O O O
Graphical LCP O O O O
Fuses S S O O
Heat sink access O O O O
Brake chopper O O O O
Regen terminals O O O O
Load share terminals – – O O
Fuses + load share – – O O
Disconnect O O – –
Circuit breakers – – – –
Contactors – – – –
24 V DC supply (SMPS, 5 A) – – – –
Dimensions
Height, mm (in) 2043 (80.4) 2043 (80.4) 1578 (62.1) 1578 (62.1)
Width, mm (in) 602 (23.7) 698 (27.5) 506 (19.9) 604 (23.9)
Depth, mm (in) 513 (20.2) 513 (20.2) 482 (19.0) 482 (19.0)
Weight, kg (lb) 295 (650) 318 (700) 272 (600) 295 (650)
Table 4.4 E1h–E4h Drives, 380–500 V
1) All power ratings are taken at high overload. Output is measured at 400 V (kW) and 460 V (hp).
2) If the enclosure is congured with load share or regen terminals, then the protection rating is IP00, otherwise the protection rating is IP20.
3) S = standard, O = optional, and a dash indicates that the option is unavailable.
Product Overview Design Guide