Danfoss VLT AutomationDrive FC 302 - Wiring Configurations for Analog Speed Reference; Wiring Configurations for Start;Stop

Danfoss VLT AutomationDrive FC 302
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB930.10
Function Setting
Parameter 1-29
Automatic Motor
Adaptation
(AMA)
[1] Enable
complete AMA
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
*=Default value
Notes/comments: Set
parameter group 1-2* Motor
Data according to motor
nameplate.
Table 12.2 Wiring Conguration for AMA without
T27 Connected
12.3
Wiring Congurations for Analog
Speed Reference
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
A53
U - I
0 – 10 V
+
-
e30bb926.11
FC
Function Setting
Parameter 6-10 T
erminal 53 Low
Voltage
0.07 V*
Parameter 6-11 T
erminal 53 High
Voltage
10 V*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 12.3 Wiring Conguration for Analog Speed Reference
(Voltage)
Parameters
+10
V
A IN
A IN
COM
A OUT
COM
50
53
54
55
42
39
+
-
FC
e30bb927.11
A53
U - I
4 - 20mA
Function Setting
Parameter 6-12 T
erminal 53 Low
Current
4 mA*
Parameter 6-13 T
erminal 53 High
Current
20 mA*
Parameter 6-14 T
erminal 53 Low
Ref./Feedb. Value
0 RPM
Parameter 6-15 T
erminal 53 High
Ref./Feedb. Value
1500 RPM
*=Default value
Notes/comments:
Table 12.4 Wiring Conguration for Analog Speed Reference
(Current)
12.4 Wiring Congurations for Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB802.10
Function Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-19 T
erminal 37 Safe
Stop
[1] Safe
Torque O
Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Table 12.5 Wiring Conguration for Start/Stop Command with
Safe Torque O
Application Examples Design Guide
MG38C202 Danfoss A/S © 01/2018 All rights reserved. 185
12 12