7.2 Electrical Data, 525–690 V
VLT
®
AutomationDrive FC 302
N55K N75K N90K N110 N132
High/normal overload HO NO HO NO HO NO HO NO HO NO
(High overload=150% current during
60 s, normal overload=110% current
during 60 s)
Typical shaft output at 525 V [kW] 45 55 55 75 75 90 90 110 110 132
Typical shaft output at 575 V [hp] 60 75 75 100 100 125 125 150 150 200
Typical shaft output at 690 V [kW] 55 75 75 90 90 110 110 132 132 160
Enclosure size D1h/D3h/D5h/D6h
Output current (3-phase)
Continuous (at 525 V) [A] 76 90 90 113 113 137 137 162 162 201
Intermittent (60 s overload)
(at 525 V) [A]
114 99 135 124 170 151 206 178 243 221
Continuous (at 575/690 V) [A] 73 86 86 108 108 131 131 155 155 192
Intermittent (60 s overload)
(at 575/690 V) [A]
110 95 129 119 162 144 197 171 233 211
Continuous kVA (at 525 V) [kVA] 69 82 82 103 103 125 125 147 147 183
Continuous kVA (at 575 V) [kVA] 73 86 86 108 108 131 131 154 154 191
Continuous kVA (at 690 V) [kVA] 87 103 103 129 129 157 157 185 185 230
Maximum input current
Continuous (at 525 V) [A] 74 87 87 109 109 132 132 156 156 193
Continuous (at 575/690 V) 70 83 83 104 104 126 126 149 149 185
Maximum number and size of cables per phase
- Mains, motor, brake, and load share
[mm
2
(AWG)]
2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0)
Maximum external mains fuses [A]
1)
160 315 315 315 315
Estimated power loss at 575 V [W]
2), 3)
1098 1162 1162 1428 1430 1740 1742 2101 2080 2649
Estimated power loss at 690 V [W]
2), 3)
1057 1204 1205 1477 1480 1798 1800 2167 2159 2740
Eciency
3)
0.98 0.98 0.98 0.98 0.98
Output frequency [Hz] 0–590 0–590 0–590 0–590 0–590
Heat sink overtemperature trip [°C (°F)]
110 (230) 110 (230) 110 (230) 110 (230) 110 (230)
Control card overtemperature trip [°C
(°F)]
75 (167) 75 (167) 75 (167) 75 (167) 75 (167)
Table 7.5 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor eciency (IE/IE3 border line). Lower eciency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
eciency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Eciency measured at nominal current. For energy
eciency class, see chapter 10.11 Eciency. For part load losses, see drives.danfoss.com/knowledge-center/energy-eciency-directive/#/.
Specications VLT® AutomationDrive FC 302
40 Danfoss A/S © 01/2018 All rights reserved. MG38C202