Parameter 24-07 Emergency Mode Feedback Source
Table 1044: Parameter 24-07 Emergency Mode Feedback Source
24-07 Emergency Mode Feedback Source
Default value: [0] No function
Change during operation: True
In emergency mode closed-loop operation, feedback is requested for the internal PID controller. Select the feedback input to be
used for the feedback signal.
N O T I C E
This option is only available in FC 302.
Parameter 24-09 Emergency Mode Alarm Handling
Table 1045: Parameter 24-09 Emergency Mode Alarm Handling
24-09 Emergency Mode Alarm Handling
Default value: [1] Trip, critical alarms
Change during operation: False
N O T I C E
Warranty-affecting alarms. Certain alarms can affect the lifetime of the drive. Should 1 of these ignored alarms occur while in
emergency mode, the alarms are logged and stored in the emergency-mode log.
N O T I C E
The setting in parameter 14-20 Reset Mode is disregarded if emergency mode is active (see parameter group 24-0* Emergency
Mode).
Select an option to define the response to alarms when emergency mode is active and an alarm is issued.
AU275636650261en-000101 / 130R0334568 | Danfoss A/S © 2022.12
Parameter Descriptions
VLT AutomationDrive FC 301/302
Programming Guide