Frame Size A1 A2 A3 A4 A5 B1 B2 B3 B4 C1 C2 C3 C4
Rated Power
[kW]
200-240V 0.25–1.5 0.25-2.2 3-3.7 0.25-2.2 0.25-3.7 5.5-7.5 11 5.5-7.5 11-15 15-22 30-37 18.5-22 30-37
380-480/500V 0.37-1.5 0.37-4.0 5.5-7.5 0.37-4 0.37-7.5 11-15 18.5-22 11-15 18.5-30 30-45 55-75 37-45 55-75
525-600V 0.75-7.5 0.75-7.5 11-15 18.5-22 11-15 18.5-30 30-45 55-90 37-45 55-90
525-690V 11-22 30-75
IP
NEMA
20
Chassis
20
Chassis
21
Type 1
20
Chassis
21
Type 1
55/66
Type 12
55/66
Type 12
21/ 55/66
Type 1/Type
12
21/55/66
Type 1/
Type 12
20
Chassis
20
Chassis
21/55/66
Type 1/
Type 12
21/55/66
Type 1/
Type 12
20
Chassis
20
Chassis
Height
Height of back plate A 200 mm 268 mm 375 mm
268
mm
375 mm 390 mm 420 mm 480 mm 650 mm 399 mm 520 mm 680 mm 770 mm 550 mm 660 mm
Height with de-coupling
plate for Fieldbus cables
A 316 mm 374 mm
374
mm
- - - - - 420 mm 595 mm 630 mm 800 mm
Distance between mounting
holes
a 190 mm 257 mm 350 mm
257
mm
350 mm 401 mm 402 mm 454 mm 624 mm 380 mm 495 mm 648 mm 739 mm 521 mm 631 mm
Width
Width of back plate B 75 mm 90 mm 90 mm
130
mm
130 mm 200 mm 242 mm 242 mm 242 mm 165 mm 230 mm 308 mm 370 mm 308 mm 370 mm
Width of back plate with
one C option
B 130 mm 130 mm
170
mm
170 mm 242 mm 242 mm 242 mm 205 mm 230 mm 308 mm 370 mm 308 mm 370 mm
Width of back plate with
two C options
B 150 mm 150 mm
190
mm
190 mm 242 mm 242 mm 242 mm 225 mm 230 mm 308 mm 370 mm 308 mm 370 mm
Distance between mounting
holes
b 60 mm 70 mm 70 mm
110
mm
110 mm 171 mm 215 mm 210 mm 210 mm 140 mm 200 mm 272 mm 334 mm 270 mm 330 mm
Depth
Depth without option A/B C 207 mm 205 mm 207 mm
205
mm
207 mm 175 mm 195 mm 260 mm 260 mm 249 mm 242 mm 310 mm 335 mm 333 mm 333 mm
With option A/B C 222 mm 220 mm 222 mm
220
mm
222 mm 175 mm 195 mm 260 mm 260 mm 262 mm 242 mm 310 mm 335 mm 333 mm 333 mm
Screw holes
c 6.0 mm 8.0 mm 8.0 mm 8.0 mm 8.0 mm 8.25 mm 8.25 mm 12 mm 12 mm 8 mm 12.5 mm 12.5 mm
d ø8 mm ø11 mm ø11 mm
ø11
mm
ø11 mm ø12 mm ø12 mm ø19 mm ø19 mm 12 mm ø19 mm ø19 mm
e ø5 mm ø5.5 mm ø5.5 mm
ø5.5
mm
ø5.5 mm ø6.5 mm ø6.5 mm ø9 mm ø9 mm 6.8 mm 8.5 mm ø9 mm ø9 mm 8.5 mm 8.5 mm
f 5 mm 9 mm 9 mm 9 mm 9 mm 6 mm 9 mm 9 mm 9 mm 7.9 mm 15 mm 9.8 mm 9.8 mm 17 mm 17 mm
Max weight 2.7 kg 4.9 kg 5.3 kg 6.6 kg 7.0 kg 9.7 kg 13.5/14.2 kg 23 kg 27 kg 12 kg 23.5 kg 45 kg 65 kg 35 kg 50 kg
Front cover tightening torque
Plastic cover (low IP) Click Click Click - - Click Click Click Click Click Click 2.0 Nm 2.0 Nm
Metal cover (IP 55/66) - - - 1.5 Nm 1.5 Nm 2.2 Nm 2.2 Nm - - 2.2 Nm 2.2 Nm 2.0 Nm 2.0 Nm
Mechanical Installation - F... FC 300 Design Guide
MG.33.BD.02 - VLT
®
is a registered Danfoss trademark 119
6
6

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals