4.5 Resumen de parámetros
0-** Operation/Display (Func. /
Display)
0-0* Basic Settings (Ajustes
básicos)
0-03 Regional Settings (Ajustes
regionales)
*[0] International (Internacional)
[1] US (EE. UU.)
0-04 Oper. State at Power-up
(Hand) (Estado operación en
arranque [Manual])
[0] Resume (Auto-arranque)
*[1] Forced stop, ref=old (Par.
forz., ref. guard)
[2] Forced stop, ref=0 (Par. forz.,
ref.=0)
0-1* Set-up Handling (Operac. de
ajuste)
0-10 Active Set-up (Ajuste
activo)
*[1] Set-up 1 (Ajuste activo 1)
[2] Set-up 2 (Ajuste activo 2)
[9] Multi Set-up (Ajuste múltiple)
0-11 Edit Set-up (Editar ajuste)
*[1] Set-up 1 (Ajuste activo 1)
[2] Set-up 2 (Ajuste activo 2)
[9] Active Set-up (Ajuste activo)
0-12 Link Set-ups (Ajustes
enlazados)
[0] Not Linked (Sin relacionar)
*[20] Linked (Relacionar)
0-31 Custom Readout Min Scale
(Valor mín. de lectura persona-
lizada)
0,00-9999,00 * 0,00
0-32 Custom Readout Max Scale
(Valor máx. de lectura persona-
lizada)
0,00-9999,00 * 100,0
0-4* LCP Keypad (Teclado del
LCP)
0-40 [Hand on] Key on LCP
(Tecla [Hand on] del LCP)
[0] Disabled (Desactivado)
*[1] Enabled (Activado)
0-41 [O / Reset] Key on LCP
(Tecla [O / Reset] del LCP)
[0] Disable All (Desactivar todo)
*[1] Enable All (Activar todo)
[2] Enable Reset Only (Sólo
activar Reset)
0-42 Tecla [Auto on] Key on LCP
(Tecla [Auto on] del LCP)
[0] Disabled (Desactivado)
*[1] Enabled (Activado)
0-5* Copy/Save (Copiar/Grabar)
0-50 LCP Copy (Copia con el
LCP)
*[0] No copy (No copiar)
[1] All to LCP (Trans. LCP tod.
par.)
[2] All from LCP (Tr d LCP tod.
par.)
[3] Size indep. from LCP (Tr d LCP
par ind tam)
0-51 Set-up Copy (Copia de
ajuste)
*[0] No copy (No copiar)
[1] Copy from set-up 1 (Copiar
desde el ajuste 1)
[2] Copy from set-up 2 (Copiar
desde el ajuste 2)
[9] Copy from Factory set-up
(Copia del ajuste de fábrica)
0-6* Password (Contraseña)
0-60 (Main) Menu Password
(Contraseña del menú principal)
0-999 *0
0-61 Access to Main/Quick Menu
w/o Password (Acceso al Menú
rápido/principal sin contraseña)
*[0] Full access (Acceso total)
[1] LCP:Read Only (LCP: solo
lectura)
[2] LCP:No Access (LCP: sin
acceso)
1-** Load/Motor (Carga/Motor)
1-0* General Settings (Ajustes
generales)
1-00 Conguration Mode (Modo
de conguración)
*[0] Speed open loop (Veloc. lazo
abierto)
[3] Process (Proceso)
1-01 Motor Control Principle
(Principio control motor)
[0] U/f
*[1] VVC+
1-03 Torque Characteristics
(Características de par)
*[0] Constant torque (Par
constante)
[2] Automatic Energy Optim.
(Optim. de la energía automática)
1-05 Local Mode Conguration
(Conguración de modo local)
[0] Speed Open Loop (Veloc. lazo
abierto)
*[2] Consulte la conguración del
par. 1-00
1-2* Motor Data (Datos motor)
1-20 Motor Power [kW] [hp]
(Potencia del motor [kW] [CV])
[1] 0,09 kW / 0,12 CV
[2] 0,12 kW / 0,16 CV
[3] 0,18 kW / 0,25 CV
[4] 0,25 kW / 0,33 CV
[5] 0,37 kW / 0,50 CV
[6] 0,55 kW / 0,75 CV
[7] 0,75 kW / 1,00 CV
[8] 1,10 kW / 1,50 CV
[9] 1,50 kW / 2,00 CV
[10] 2,20 kW / 3,00 CV
[11] 3,00 kW / 4,00 CV
[12] 3,70 kW / 5,00 CV
[13] 4,00 kW / 5,40 CV
[14] 5,50 kW / 7,50 CV
[15] 7,50 kW / 10,00 CV
[16] 11,00 kW / 15,00 CV
[17] 15,00 kW / 20,00 CV
[18] 18,50 kW / 25,00 CV
[19] 22,00 kW / 29,50 CV
[20] 30,00 kW / 40,00 CV
1-22 Motor Voltage (Tensión del
motor)
50-999 V *230-400 V
1-23 Motor Frequency
(Frecuencia del motor)
20-400 Hz *50 Hz
1-24 Motor Current (Intensidad
del motor)
0,01-100,00 A *Dep. tipo motor
1-25 Motor Nominal Speed
(Velocidad nominal de motor)
100-9999 r/min * Dep. tipo
motor
1-29 Automatic Motor Tuning
(AMT) (Ajuste automático del
motor [AMT])
*[0] O (Desactivado)
[2] Enable AMT (Activar AMT)
[3] Complete AMT with Rotating
motor (AMT completo con motor
en giro)
1-3* Adv. Motor Data (Datos
avanz. del motor)
1-30 Stator Resistance (Rs)
(Resistencia del estátor [Rs])
[Ω] * Dep. de datos del motor
1-33 Stator Leakage Reactance
(X1) (Reactancia de fuga del
estátor [X1])
[Ω] * Dep. de datos del motor
1-35 Main Reactance (Xh)
(Reactancia principal [Xh])
[Ω] * Dep. de datos del motor
1-5* Load Indep. Setting (Aj.
indep.de la carga)
1-50 Motor Magnetisation at 0
Speed (Magnetización del
motor a velocidad cero)
0-300 % *100 %
1-52 Min Speed Norm. Magnet.
(Magnetización normal a
velocidad mínima) [Hz]
0,0-10,0 Hz *0,0 Hz
1-55 U/f Characteristic - U
(Característica U/f - U)
0-999,9 V
1-56 U/f Characteristic - F
(Característica U/f - F)
0-400 Hz
1-6* Load Depen. Setting (Aj.
depend.de la carga)
1-60 Low Speed Load Compen-
sation (Compensación de carga
a baja velocidad)
0-199 % *100 %
1-61 High Speed Load Compen-
sation (Compensación de carga
a alta velocidad)
0-199 % *100 %
1-62 Slip Compensation
(Compensación de desliza-
miento)
-400-399 % *100 %
1-63 Slip Compensation Time
Constant (Constante de tiempo
de compensación de desliza-
miento)
0,05-5,00 s *0,10 s
1-7* Start Adjustments (Ajustes
del arranque)
1-71 Start Delay (Retardo de
arranque)
0,0-10,0 s *0,0 s
1) Solo M4 y M5
Guía rápida
Quick GuideKurzanleitungGuide rapideGuía rápidaGuia RápidoКраткое
руководство
MG02BB4P Danfoss A/S © 05/2016 All rights reserved. 91
4 4

Table of Contents

Other manuals for Danfoss VLT Micro Drive FC 51

Related product manuals