Data Aire DAP III - System Configuration and Menus; Programmable Selections & Menu Structure

Data Aire DAP III
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Network Variable Network Variable Type Description Units
two-with-limits(3)
one-no-limits(4)
two-no-limits(5)
1.3.6.1.4.1.22731.1.2.1.107.0 INTEGER
none(1)
one-heat-strip(2)
two-heat-strips(3)
three-heat-strips(4)
hot-water(5)
Heater Configuration
Factory setting
N/A
1.3.6.1.4.1.22731.1.2.1.108.0 INTEGER
none(1)
computer-non-modutating(2)
computer-modulating(3)
comfort-non-modulating(4)
comfort-modulating(5)
Humidifier Configuration
Factory setting
N/A
1.3.6.1.4.1.22731.1.2.1.110.0 INTEGER
auto(1)
one-leads(2)
two-leads(3)
three-leads(4)
four-leads(5)
Lead-Lag Configuration
N/A
1.3.6.1.4.1.22731.1.2.1.111.0 INTEGER (0..1000)
Maintenance Interval
Hours
1.3.6.1.4.1.22731.1.2.1.112.0 INTEGER (0..99)
Front Panel Password
N/A
1.3.6.1.4.1.22731.1.2.1.113.0 INTEGER
not-used(1)
data-processing-manager(2)
maintenance-engineer(3)
service-company(4)
custom-contact-message(5)
Person To Contact
N/A
1.3.6.1.4.1.22731.1.2.1.114.0 INTEGER
auto-no-message-or-alarm(1)
auto-message-and-alarm(2)
manual-msg-alarm-relay(3)
Reset Mode
N/A
1.3.6.1.4.1.22731.1.2.1.115.0 INTEGER
off(1),
short(2)
long(3)
full(4)
Buzzer Configuration
N/A
1.3.6.1.4.1.22731.1.2.1.116.0 OCTET STRING
Each octet represents the index of
one current alarm from the
following table.
waterDetected(1)
noAirFlow(2)
dirtyFilter(3)
humidifierProblem(4)
lowVoltage(5)
fireAlarm(6)
shortCycle(7)
powerProblem(8)
humiditySensor(9)
temperatureSensor(10)
maintenanceRequired(11)
Alarm Relay 1 Settings
N/A
Document 600-000-615
12