MAINTENANCE/INSPECTION CHECKLIST
Humidier (Steam Generator) is equipped
___ Inspect drain valve/trap/drain line
___ Check for leaks (make-up water/hoses)
___ Check humidier canister (replace if needed)
___ Check and clean ll strainer
___ Check operation
___ Record humidier amp draw L1_____ L2 _____ L3 _____
Reheat
___ Inspect element (and clean if required)
___ Check wiring
___ Record amps ______ A
Refrigeration Piping
___ Check for lines (leaks/lines secure)
___ Check capillary lines
Condensers (Water-Cooled)
___ Check for leaks
___ Entering/leaving water temperatures ENT ____°F LVG ____°F
Compressor (Monthly)
___ Check for oil leaks
___ Check compressor mounting
___ Inspect wire connection
Compressor (Quarterly) Compressor 1 Compressor 2
___ Record suction pressure ______ PSIG ______ PSIG
___ Record discharge pressure ______ PSIG ______ PSIG
___ Record superheat ______ °F ______ °F
___ Record sub-cooling ______ °F ______ °F
___ Check high pressure cut-out ______ PSIG ______ PSIG
___ Check low pressure cut-in ______ PSIG ______ PSIG
___ Check low pressure cut-out ______ PSIG
___ Record compressor amp draw ______ L1 ______ L1
______ L2 ______ L2
______ L3 ______ L3