gForce Ultra IOM
101
Multiple EEV Configuration
For single circuit units, there will be one EEV and it will be shown as valve A. The letter “A”
will be displayed on the top right corner of the EVD display screen, near the “ON” status. For a
dual circuit unit, there will be two EEVs and the second valve will be displayed as valve B. Set up
for valve A does not affect settings for valve B, therefore, when the unit has two EEVs, set up for
valve B is required.
To setup valve B for circuit #2, press the two furthest keys simultaneously (ALARM + ENTER).
The letter “B” will appear on the top right corner of the display. The display will now show the
refrigerant status of circuit #2.
WARNING: Valve B must to be configured the same as Valve A in
Configuration Menu and Regulation Menu.