gForce Ultra IOM
113
MAINTENANCE/INSPECTION CHECKLIST
MAINTENANCE/INSPECTION CHECKLIST
(NOTE: Maintenance/inspection items are monthly unless otherwise specified.)
Evaporator Model No.:
Evaporator Serial No.:
Technician:
Date:
Temperature/Humidity set at:
°F % RH
Air Filters:
Inspect and replace (if required)
Inspect grille area and ensure unrestricted
Air Distribution Section
Check restriction of grilles and discharge
louvers
Electrical Section
Inspect fuses
Inspect/tighten all wire connections
Inspect contactor operation
Check operation sequence
Check calibration of change over
thermostat (Energy Saver system only)
Controls
Check unit control operation
Check operation of the following:
High water alarm
Pressure differential switch
Fan current sensing switch
EC Plug Fan Section:
Check plug fan wheel movement to be free and clear of any debris
Record motor voltage Record motor amp draw
Fan#1 L1 V L2 V L3 V L1 A L2 A L3 A
Fan#2 L1 V L2 V L3 V L1 A L2 A L3 A
Fan#3 L1 V L2 V L3 V L1 A L2 A L3 A
Record fan wheel speed (RPM) Fan#1 RPM Fan#2 RPM Fan#3 RPM
Humidifier (Steam Generator) is equipped:
Inspect drain valve/trap/drain line Check for leaks (make-up water/hoses)
Check humidifier canister (replace if needed) Check and clean fill strainer
Check operation
Record humidifier amp draw L1 A L2 A L3 A
Reheat