VFD parameter settings - Danfoss CDS-803 Drive (22 kW Ultra units)
Figure 17 CDS-803 Drive P/N 101-260-230 or 460-VFD (22 kW Ultra units)
Menu ID
Description
Setting
3.** Reference / Ramps
3.0* Reference Limits
3-02
Minimum Reference
30 Hz
3.4* Ramp 1
3-41
Ramp 1 Ramp Up Time
120s
3-42
Ramp1 Ramp Down Time
300s
4.** Limits / Alarms
4.1* Motor Limits
4-18
Current Limit
110%
5.** Digital In/Out
5.1* Digital Inputs
5-12
Terminal 27 Digital Input
[0] No operation
VFDs built after 7/2017 - last 3 digits of serial number indicate the month and year of manufacture: *******468, 46th week of 2018.
5-12
Terminal 27 Digital Input
[2] Coast Inverse
VFDs built before 7/2017 - last 3 digits of serial number indicate the month and year of manufacture: *******047, 4th week of 2017.
5.4* Relays
5-40
Function Relay
[0] [9] Alarm
[1] [5] Drive Running
8.** Comm. And Options
8.3* FC Port Settings
8-30
Protocol
Modbus RTU
8-31
Address
19
8-32
Baud Rate
19,200
8-33
Parity / Stop Bits
No Parity / 1 Stop Bit
28.** Compressor Functions
28.0* Short Cycle Protection
28-00
Short cycle protection
[0] Disable
28.1* Oil Return Management
28-10
Oil Return Management
[1] On
28-11
Low Speed Running Time
60 min (Minutes)
28-12
Fixed Boost Interval
1 H (Hour)
28-13
Boost Duration
60 s (Seconds)